IEinführung
The risk of overheating is becoming more serious due to the fact that today’s distribution networks have to carry heavier loads. Checking contact resistance at regular intervals detects faults before they cause overheating. Contact resistance tester is used to measure contact resistances of circuit breakers, disconnecting switches, earthing switches, bus joints, bushing contact joints and welding joints. Also for any low resistance measuring application. The tester provide 100A DC current, and the voltage measurement gets the voltage of tested object. The method of calculate resistance according to Ohm & #39;s law. (R=U/I)
Eigenschaften
● Setting current output time between 1s to 60s.
● Save the device & #39;s series number, for checking the result conveniently.
● Zeigen Sie während des Tests Ausgangsstrom, Ausgangszeit und Widerstand an.
● Saving 100 test results in tester memory.
● Eingebaute - Uhr zeichnet das Datum auf.
● The stored result includes device & #39;s number, testing time and resistance.
Spezifikationen
ZD1C |
Test current: 100A |
Output power: 1kW |
Messbereich: 0. 1μΩ bis 20000μΩ |
Genauigkeit: ± 0. 5% rdg ± 0. 2μΩ |
Auflösung: {{0}}. 1μΩ bis 999,9μΩ , Auflösung: 0. 1μΩ 1000μΩ to 20000μΩ, Resolution:1μΩ |
Amperemeter-Genauigkeit: ± {{0}}. 5% rdg ± 0. 1A |
Dimensions: 403×330×178mm Weight: 7kg |
Allgemeines |
Memory capacity: 100 results |
Power supply: 198 to 264VAC 47 to 63Hz |
Umgebung: -20 bis 50 ℃ Luftfeuchtigkeit ≤ 90% rF Nicht - kondensierend |
http://de.handy-analyzer.com/